Danger – Enviro 6G50 76N Manuel d'utilisation

Page 30

Advertising
background image

30

methods can increase the rate of anode rod depletion. Once the anode rod

is depleted, the tank will start to corrode, eventually developing a leak.

Certain water conditions will cause a reaction between the anode rod

and the water. The most common complaint associated with the anode

rod is a “rotten egg smell” produced from the presence of hydrogen

sulfide gas dissolved in the water. IMPORTANT: Do not remove this

rod permanently as it will void any warranties. The parts list includes a

special anode rod that can be ordered if water odor or discoloration occurs.

NOTE: This rod may reduce but not eliminate water odor problems. The

water supply system may require special filtration equipment from a water

conditioning company to successfully eliminate all water odor problems.

Artificially softened water is exceedingly corrosive because the

process substitutes sodium ions for magnesium and calcium ions. The

use of a water softener may decrease the life of the water heater tank.

The anode rod should be removed from the water heater tank every

3 years for inspection. NOTE: artificially softened water requires the

anode rod to be inspected annually.

The following are typical (but not all) signs of a depleted anode rod:

* The majority of the rods diameter is less than 3/8”.

* Significant sections of the support wire (approx. 1/3 or more of the

anode rod’s length) are visible.

If the anode rod show signs of either or both it should be replaced.

NOTE: Whether re-installing or replacing the anode rod, check for

any leaks and immediately correct if found.

In replacing the anode:

1. Turn off gas supply to the water heater.
2. Shut off the water supply and open a nearby hot water faucet to

depressurize the water tank.
3. Drain approximately 5 gallons of water from tank (Refer to “Draining

and Flushing” for proper procedures). Close drain valve.
4. Remove old anode rod.
5. Use Teflon® tape or approved pipe sealant on threads and install

new anode rod.
6. Turn on water supply and open nearby hot water faucet to purge air

from water system. Check for any leaks and immediately correct

any if found.

Restart the water heater as directed under “Operating Your Water

Heater.” See the Repair Parts Illustration for anode rod location.

fIGure 28.

teMperature-pressure relIef valve test

DANGER

Burn hazard.

Hot water discharge.

Keep clear of Temperature-

Pressure Relief Valve

discharge outlet.

It is recommended that the Temperature-Pressure Relief Valve should

be checked to ensure that it is in operating condition every 6 months.

When checking the Temperature-Pressure Relief Valve operation, make

sure that (1) no one is in front of or around the outlet of the Temperature-

Pressure Relief Valve discharge line, and (2) that water discharge will

not cause any property damage, as water may be extremely hot. Use

care when operating valve as the valve may be hot.

To check the relief valve, lift lever at the end of valve several times,

see Figure 29. The valve should seat properly and operate freely.

If after manually operating the valve, it fails to completely reset and

continues to release water, immediately close the cold water inlet to

the water heater and drain the water heater, see Draining And Flushing

on page 30-31. Replace the Temperature-Pressure Relief Valve with a

properly rated/sized new one, see Temperature-Pressure Relief Valve

on page 15-16 for instructions on replacement.

DISCHARGE PIPE

TEMPERATURE-PRESSURE

RELIEF VALVE

fIGure 29.

If the Temperature-Pressure Relief Valve on the water heater weeps

or discharges periodically, this may be due to thermal expansion.

Note: Excessive water pressure is the most common cause of

Temperature-Pressure Relief Valve leakage. Excessive water system

pressure is most often caused by “thermal expansion” in a “closed

system.” See Closed Water Systems and Thermal Expansion on page

14-15. The Temperature-Pressure Relief Valve is not intended for the

constant relief of thermal expansion.

Temperature-Pressure Relief Valve leakage due to pressure build

up in a closed system that does not have a thermal expansion tank

installed is not covered under the limited warranty. Thermal expansion

tanks must be installed on all closed water systems.

do not pluG the teMperature-pressure relIef valve

openInG. thIs can cause propertY daMaGe, serIous

InjurY or death.

Explosion Hazard

Temperature-Pressure Relief Valve

must comply with ANSI Z21.22-

CSA 4.4 and ASME code.

Properly sized Temperature-Pressure

Relief Valve must be installed in

opening provided.
Can result in overheating and

excessive tank pressure.
Can cause serious injury or death.

draInInG and flushInG

It is recommended that the water heater storage tank be drained

and flushed every 6 months to reduce sediment buildup. The

water heater should be drained if being shut down during freezing

temperatures. See Typical Installation section in this manual

for location of the water heater components described below.

Advertising