7. Take the other end of the flexible tubing and slide it through

the hose clamp on the jacket top cover and install it into one

of the four barb fittings in vent pipe assembly #2.

8. Once installed along with the rest of the vent configuration, make

sure to operate the unit through at least one heat up cycle to

ensure there is no leakage around the hose barb or any joints

of the VAA or vent pipe system.

fIGure 23: typical horizontal Installation

Installation for VAA with 3 & 4 inch Pipe for Vertical Vent

Some applications may require the use of 3 or 4 inch vent pipe for
longer vent lengths. Please refer to Figure 24 as you review these
instructions. Refer back to the vertical VAA installation steps but with
the following changes to the vent construction.

3 inch vent (Vertical VAA Installations)

The VAA is designed to accommodate only 2 inch vent pipe. The
installer must use 2 inch vent pipe between the blower assembly
and the inlet into the VAA. On the outlet side of the VAA, a short
run of 2 inch vent pipe is required. Each of the short pieces of 2
inch pipe entering and exiting the VAA must not exceed 6 inches
(15 cm) in length. From this point on, a 2 inch to 3 inch adapter
may be used. From the 2 inch to 3 inch adapter, the installer may
use up to 65 equivalent feet (19.8 m) of pipe, see Figure 24 for
typical installation.

4 inch vent (Vertical VAA Installations)

The VAA is designed to accommodate only 2 inch vent pipe. The
installer must use 2 inch vent pipe between the blower assembly
and the inlet into the VAA. On the outlet side of the VAA, a short
run of 2 inch vent pipe is required. Each of the short pieces of 2
inch pipe entering and exiting the VAA must not exceed 6 inches
(15 cm) in length. From this point on, a 2 inch to 4 inch adapter
may be used. From the 2 inch to 4 inch adapter, the installer may
use up to 128 equivalent feet (39.0 m) of pipe, see Figure 24 for
typical installation.

remember to operate the unit for at least one heat cycle to

ensure there are no air leaks in the vent joints of the vaa and

the vent pipe system. Air leaks will allow flue gas by-products to

disseminate into the room creating an unsafe environment and

could cause illness, asphyxiation and/or even death.

FIGURE 24: Typical Installation for Vertical Vent with 3 or 4 inch Pipe

note: Since neither hose barb nor flexible tubing is used on the

VAA, any unused open barb fittings on vent pipe assembly #2

need to be plugged using break-away plugs.
Installation of VAA with 3 & 4 inch Pipe for Horizontal Vent

Some applications may require the use of 3 or 4 inch vent pipe for

longer vent lengths. Please refer to the Figure 25 as you review these

instructions. Refer back to the horizontal VAA installation steps but

with the following changes to the vent construction.
3 inch vent (Horizontal VAA Installations)

The VAA is designed to accommodate only 2 inch vent pipe. The

installer must use 2 inch vent pipe between the blower assembly and

the inlet into the VAA. On the outlet side of the VAA, a short run of 2

inch vent pipe is required. From this point on, a 2 inch to 3 inch adapter

may be used. From the 2 inch to 3 inch adapter, the installer may use

up to 52 equivalent feet (15.8 m) of pipe. This is 8 equivalent feet (2.4

m) less than the original 60 equivalent feet (18.3 m) specified with

one elbow due to the 2 inch elbow instead of a 3 inch elbow required

for the vent from the blower to the inlet of the VAA, see Figure 25 for

typical installation.
4 inch vent (Horizontal VAA Installations)

The VAA is designed to accommodate only 2 inch vent pipe. The installer

must use 2 inch vent pipe between the blower assembly and the inlet into

the VAA. On the outlet side of the VAA a short run of 2 inch vent pipe is

required. From this point on, a 2 inch to 4 inch adapter may be used. From

the 2 inch to 4 inch adapter, the installer may use up to 102 equivalent feet

(31.1 m) of pipe. This is 18 equivalent feet (5.5 m) less than the original

120 equivalent feet (36.6 m) specified with one elbow due to the 2 inch

elbow instead of a 4 inch elbow required for the vent from the blower to

the inlet of the VAA, see Figure 25 for typical installation.
remember to operate the unit for at least one heat cycle to ensure

there are no air leaks in the vent joints of the vaa and the vent pipe

system. Air leaks will allow flue gas by-products to disseminate

into the room creating an unsafe environment and could cause

illness, asphyxiation and/or even death.

FIGURE 25: Typical Installation for Horizontal Vent with 3 or 4 inch Pipe