98

Rockwell Automation Publication 1440-UM001C-EN-P - May 2014

Chapter 3

Operate the Module

Modes

The XM-124 module operates in two modes.

To change the operation mode of the module, use the parameter in the EDS file.
Note that the Stop and Start services can also be used to change the operation
mode.

Transition to Program Mode

Parameter values can only be downloaded to the XM-124 module while the
module is in Program mode. Any attempt to download a parameter value while
the module is in Run mode results in a Device State Conflict error.

To transition from Run mode to Program mode on a DeviceNet network, set the
Device Mode parameter to Program mode and click Apply. Note that you cannot
change any other parameter until you have downloaded the Program mode
parameter.

Refer to your DeviceNet documentation for specific instructions on editing EDS
device parameters.

Mode

Description

Run

The XM-124 standard dynamic measurement module collects measurement data and
monitors each measurement device.

The XM-440 establishes I/O connections with the XM measurement modules in its
scan list and monitors their alarms, and controls its own relay outputs accordingly.

Program

The XM-124 module is idle.

The XM-124 measurement modules stop the signal processing/measurement
process, and the status of the alarms is set to the disarm state to prevent a false alert
or danger status.

The XM-440 closes the I/O connections with the XM measurement modules in its scan
list and stops monitoring their alarms, relays are deactivated unless they are latched.
Configuration parameters can be read, updated and downloaded to the XM-124
module.

IMPORTANT

The XM Serial software automatically puts the XM-124 module in Program
mode and Run mode without user interaction.

TIP

The Module Status indicator flashes green when the module is in Program
mode.

TIP

You can also use the Stop service to transition the module to Program
mode.