Install the XM-124 Standard Dynamic Measurement Module

Chapter 1

Figure 26 - IEPE Accelerometer and Non-contact Sensor Wiring

Connect Two Accelerometers and a Non-Contact Sensor

The following figure shows the wiring of two IEPE accelerometers and a non-
contact sensor to the terminal base. The IEPE accelerometers are wired to
channel 1 and channel 2. The non-contact sensor is wired to the tachometer
input signal.

TYPICAL WIRING FOR IEPE ACCELEROMETER AND NON-CONTACT

SENSOR TO XM-120/1 21 DY NAMIC MEASUREME NT MODULE

Shield

Pin A - Signal
Pin B - Co mmo n

Cable shield not
conn ecte d at this end

0

16

22

6

21

Channel 1 Input Signal

Signal Common

5

37

SIG

-24

COM

17

1

Signal Common
Channel 2 Input Signal

-24V DC

13

Shield

S h ield F loating

Isolated Sensor Driver

*

*

*Note: Jumpering terminal 5 to terminal 6
configures CH 1 buffer (-5V to +24V)

Jumpering terminal 21 to terminal 22
configures CH 2 buffer (-24V to +9V)

TYPICAL WIRING FOR IFPF ACCELEROMETER AND NON-CONTACT
SENSOR TO XM-124 STANDARD DYNAMIC MEASUREMENT MODULE

WARNING: You may ground the cable shield at either end of the cable.
Do not ground the shield at both ends. Recommended practice is to
ground the cable shield at the terminal base and not at the transducer.
Any convenient chassis terminal may be used (see

Terminal Block

Assignments on page 27

).

IMPORTANT

Make certain the IEPE Power parameter is enabled for both channel 1 and
channel 2 so power is provided to the accelerometers.

Refer to Transducer

Object (Class ID 328H) on page 154

.

IMPORTANT

Transducer DC bias is monitored on all signals.