The XM-124 module Poll request message contains no data. The Poll response
message can contain up to 44 REAL values for a total of 176 bytes.

The XM-124 module provides one pre-defined (static) data format of the Poll
response, defined in Assembly instance 101. It also provides a dynamic Assembly
instance, instance 199, with which you can define a custom data format for the
Poll response. The dynamic Assembly instance can contain any of the
measurement parameters included in Assembly instance 101, as well as several of
the alarm and relay configuration parameters.

The default Assembly instance is 101 and the default size is 20 bytes. You can
change the Assembly instance and define the custom Assembly instance using the
configuration software. Refer to

I/O Data Tab on page 89

.

The Poll response data can also be requested explicitly through Assembly Object
(Class ID 0x4), Instance 101 (0x65), Data Attribute (3). When you explicitly
request the Data Attribute for Assembly instance 101, it returns the entire 176
bytes.

The following tables show the static data format of Assembly instance 101.

Table 16 - XM-124 Module Assembly Instance 101 Data Format

Byte

Definition

0…3

Channel 1 Overall measurement value

4…7

Channel 2 Overall measurement value

8…11

Channel 1 Gap measurement value

12…15

Channel 2 Gap measurement value

16…19

Current Speed measurement value

20…23

Peak Speed measurement value

24…27

Channel 1 Band 1 measurement value

28…31

Channel 2 Band 1 measurement value

32…35

Channel 1 Band 2 measurement value

36…39

Channel 2 Band 2 measurement value

40…43

Channel 1 Band 3 measurement value

44…47

Channel 2 Band 3 measurement value

48…51

Channel 1 Band 4 measurement value

52…55

Channel 2 Band 4 measurement value

56…59

Channel 1 1X Vector Magnitude measurement value

60…63

Channel 1 1X Vector Phase measurement value

64…67

Channel 2 1X Vector Magnitude measurement value

68…71

Channel 2 1X Vector Phase measurement value

72…75

Channel 1 2X Vector Magnitude measurement value

76…79

Channel 1 2X Vector Phase measurement value