Rockwell Automation Publication 1440-UM001C-EN-P - May 2014

73

Configure the XM-124 Standard Dynamic Measurement Module

Chapter 2

gSE Measurement Options

The gSE Measurement options apply to the Alternating gSE and Continuous gSE
measurement modes. These settings affect the gSE Overall or gSE FFT
measurements.

In this field

Values are

Comments

Full Scale

The maximum signal level expected to be processed by the channel for
gSE measurements. This value is used to determine the programmable
gain settings across each stage of the channel’s analog signal processing
circuit.

The default value is 20 gSE.

High Pass Filter

Choose the high pass filter to apply to the gSE measurement.
200 Hz
500 Hz
1000 Hz
2000 Hz
5000 Hz

The high pass filter is useful in removing low frequency signal
components that could otherwise dominate the signal. The
high pass filter attenuates frequencies less than the selected
frequency. It allows, or passes, frequencies greater than the
selecteded frequency.

Frequency maximum

Enter the maximum frequency for the gSE spectrum, 10 to 5000 Hz.

The gSE spectrum always uses asynchronous sampling mode
and the FMAX is always in Hz.

Number of lines

Choose the number of lines (bins) in the gSE spectrum measurement:
100
200
400
800
1600

This determines the frequency resolution of the gSE
spectrum.