Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation

Page 29

Advertising
background image

Rockwell Automation Publication 1440-UM001C-EN-P - May 2014

29

Install the XM-124 Standard Dynamic Measurement Module

Chapter 1

1

Terminals are internally connected and isolated from the chassis terminals.

20

Tachometer (-)

Tachometer transducer/signal return, TACH Buffer return

21

Buffer/Xducer Pwr (-)

Provides negative (-24 V to +9 V) voltage compliance to buffered outputs
Connect to terminals 5 (CH 1) and 22 (CH 2) for negative bias transducers
Transducer power supply output, negative side; used to power external sensor (40 mA maximum
load)

22

Buffer Power 2 IN

Channel 2 buffer power input
Connect to terminal 6 for positive biased transducers or terminal 21 for negative biased
transducers

23

CAN_High

DeviceNet bus connection, high differential (white wire)

24

CAN_Low

DeviceNet bus connection, low differential (blue wire)

25

+24 V Out

Internally connected to 24 V In

1

(terminal 44)

Used to daisy chain power if XM modules are not plugged into each other
If power is not present on terminal 44, there is no power on this terminal

26

DNet V (+)

DeviceNet bus power input, positive side (red wire)

27

DNet V (-)

DeviceNet bus power input, negative side (black wire)

28

24 V Common

1

Internally connected to 24 V Common (terminals 43 and 45)
Used to daisy chain power if XM modules are not plugged into each other

29

4…20 mA 2 (+)

4…20 mA output
300 ohm maximum load

30

4…20 mA 2 (-)

31

Chassis

Connection to DIN rail ground spring or panel mounting hole

32

Chassis

Connection to DIN rail ground spring or panel mounting hole

33

Chassis

Connection to DIN rail ground spring or panel mounting hole

34

Chassis

Connection to DIN rail ground spring or panel mounting hole

35

Chassis

Connection to DIN rail ground spring or panel mounting hole

36

Chassis

Connection to DIN rail ground spring or panel mounting hole

37

Chassis

Connection to DIN rail ground spring or panel mounting hole

38

Chassis

Connection to DIN rail ground spring or panel mounting hole

39

SetPtMult

Switch input to activate Set Point Multiplication (active closed)

40

Switch RTN

Switch return, shared between SetPtMult and Reset Relay

41

Reset Relay

Switch input to reset internal relay (active closed)

42

Reserved

43

24 V Common

1

Internally DC-coupled to circuit ground

44

+24 V In

Connection to primary external +24 V power supply, positive side

45

24 V Common

1

Connection to external +24 V power supply, negative side (internally DC-coupled to circuit
ground)

46

Reserved

47

Relay Common

Relay Common contact

48

Relay N.O.

Relay Normally Open contact

49

Reserved

50

Reserved

51

Reserved

Table 2 - Terminal Block Assignments

No.

Name

Description

Advertising