Chapter 1

Install the XM-124 Standard Dynamic Measurement Module

Connect an IEPE Accelerometer and Non-contact Sensor

The following figure shows the wiring of an IEPE accelerometer to channel 1 and
the wiring of a non-contact sensor to channel 2.

ATTENTION: You may ground the cable shield at either end of the cable.
Do not ground the shield at both ends. Recommended practice is to
ground the cable shield at the terminal base and not at the transducer.
Any convenient chassis terminal may be used (see

Terminal Block

Assignments on page 27

).

IMPORTANT

Make certain the IEPE Power parameter for channel 1 is enabled so power
is provided to the accelerometer.

Refer to Transducer Object (Class ID 328H)

on page 154

.

IMPORTANT

The internal transducer power supply is providing power to the non-contact
sensor.

IMPORTANT

A jumper from terminal 5 to terminal 6 is required for channel 1 buffered
output. A jumper from terminal 22 to terminal 21 is required for channel 2
buffered output.

See Connect the Buffered Outputs on page 33

.