22

Rockwell Automation Publication 1440-UM001C-EN-P - May 2014

Chapter 1

Install the XM-124 Standard Dynamic Measurement Module

Figure 6 - Panel/Wall Mount Grounding

1

Use 2.1 mm

2

(14 AWG) wire. If it is desired to isolate the power supply because of possible ground loops, do not connect 24V

common to earth, as illustrated.

2

Use 8.4 mm

2

(8 AWG) wire.

24V Common Grounding

The XM system is sourced by a single Class 2 power supply. We recommend that
the 24V power to the XM modules is grounded.

1

1

Class 2

Supply

Class 2

Supply

2