Rockwell Automation Publication 1440-UM001C-EN-P - May 2014

135

CIP Objects

Appendix B

Instance Attributes

Table 54 - Alarm Object Instance Attributes

Attr ID

Access Rule

Name Data

Type

Description

Semantics

3

Get

Alarm Status

3 BITS

The current status of the alarm.

0 = Normal
1 = Alert (alarm)
2 = Danger (shutdown)
3 = Disarm
4 = Xdcr Fault
5 = Module Fault
6 = Tachometer Fault

4

Get/Set

Alarm Enable

BOOL

Indicates whether this alarm
object is enabled.

0 = Disabled
1 = Enabled

5

Get

Type

USINT

Type of Alarm

0 = Magnitude
1 = Vector

6

Get

Threshold Units

USINT

Indicates whether the thresholds
and deadband value are specified
in units of measure. Not applicable
to vector alarms.

Set to 1
1 = Measurement units

7

Get/Set

AlarmCondition

USINT

Indicates on which side of the
threshold values the alarm and
danger conditions exist. Not
applicable to vector alarms.

0 = Greater than
1 = Less than
2 = Inside range
3 = Outside range

8

Get/Set

AlarmHAlertLimit

REAL

The threshold value for the alert
state of the alarm. (For range
conditions, this is the greater
threshold value.)

9

Get/Set

AlarmHDangerLimit

REAL

The threshold value for the Danger
state of the alarm. (For range
conditions, this is the greater
threshold value).

10

Get/Set

AlarmLAlertLimit

REAL

The lesser threshold value for the
Alert state of the alarm with a
range condition type.

11

Get/Set

AlarmLDangerLimit

REAL

The lesser threshold value for the
Danger state of the alarm with a
range condition type.

12

Get/Set

AlarmDeadband

REAL

The amount on the safe side of a
threshold by which the value must
recover to clear the alarm.

13

Get/Set

AlarmLimitMultiply (Setpoint
Multiplier)

REAL

Indicates how the threshold must
be adjusted when the setpoint
multiplication function is invoked.

0 = Disable alarm
> 0 = Multiply the thresholds by the value

14

Get/Set

AlarmLimitMultiplyPeriod

UINT

The amount of time that the
Threshold (Setpoint) Multiplier is
applied after the start-up signal is
received.

Seconds

15

Get/Set

AlarmSpeedRangeEn

BOOL

Indicates whether this alarm is
enabled only within a certain
machine speed range.

0 = No speed range (alarm is always
enabled)
1 = Speed range (alarm only enabled
within speed range)

16

Get/Set

AlarmSpeedHLimit

REAL

Indicates the greater threshold of
the machine speed range for
which the alarm is enabled
(disabled at greater speeds).

CPM
(must be greater than
AlarmSpeedLLimit)