Rockwell Automation Publication 1440-UM001C-EN-P - May 2014

129

CIP Objects

Appendix B

7

No

4-20 mA Output 1 Measurement
Identifier

USINT

0 = CH 1 Overall
1 = CH 2 Overall
2 = CH 1 Gap
3 = CH 2 Gap
4 = CH 1 Band 1
5 = CH 2 Band 1
6 = CH 1 Band 2
7 = CH 2 Band 2
8 = CH 1 Band 3
9 = CH 2 Band 3
10 = CH 1 Band 4
11 = CH 2 Band 4
12 = Speed
13 = SMAX Mag.
14 = CH 1 1X Mag.
15 = CH 2 1X Mag.
16 = CH 1 2X Mag.
17 = CH 2 2X Mag.
18 = CH 1 3X Mag.
19 = CH 2 3X Mag.
20 = CH 1 Not 1X
21 = CH 2 Not 1X
22 = CH 1 Sum Harmonics
23 = CH 2 Sum Harmonics
29 = Acceleration
30 = CH1 Thrust Position
31 = CH2 Thrust Position
32 = CH1 gSE Overall
33 = CH2 gSE Overall
34 = CH1 Eccentricity
35 = CH2 Eccentricity
36 = CH1 gSE Band Pass
37 = CH2 gSE Band Pass
38 = CH1 gSE Tracking Mag.
39 = CH2 gSE Tracking Mag.

0

8

No

4-20 mA Output 2 Measurement
Identifier

USINT

(same as above)

1

9

No

Transducer 3 (Tachometer) Sensitivity
Units

USINT

0 = mil
1 = in/s
2 = g
3 = psi
4 = volts
5 = mm/s
6 = μm
7 = Pa
8 = mbar

0

Table 48 - Parameter Object Instances

Instance

Read
Only

Name

Data Type

Valid Values

Default Value