Install the XM-124 Standard Dynamic Measurement Module

Chapter 1

Figure 16 - IEPE Accelerometer to Channel 1 Wiring

Figure 17 - IEPE Accelerometer to Channel 2 Wiring

TYPI CAL WIRI NG FOR IEPE ACCELEROMETER

TO XM-120/121DYNAMIC MEASUREM ENT MO DULE CHANNEL 1

Shield

Pin A - Si gn al
Pin B - Com mon

Cable shield not
conn ecte d at this end

0

16

6

Channel 1 Input Signal

Signal Common

5

37

Jumpering terminal 5
to terminal 6 configures
CH 1 buffer for -5V to +24V

TYPICAL WIRING FOR IEPE ACCELEROMETER
TO XM-124 STANDARD DYNAMIC MEASUREMENT MODULE CHANNEL 1

TYPICAL WIRING FOR IEPE ACCELEROMETER

TO XM-120/ 121 DYNAMIC MEASUREMENT MODUL E CHANNEL 2

Shi eld

Pin A - Signal
Pin B - Common

Cabl e shield not
conn ecte d at this end

1

17

6

Channel 1 Input Signal

Signal Common

38

Jumpering terminal 6 to
terminal 22 configures
CH 2 buffer for -5V to +24V

Channel 2 Input Signal

22

TYPICAL WIRING FOR IEPE ACCELEROMETER
TO XM-124 STANDARD DYNAMIC MEASUREMENT MODULE CHANNEL 2