Chapter 1

Install the XM-124 Standard Dynamic Measurement Module

Connecting Power

Power supplied to the module must be nominally 24V DC (±10%) and must be a
Class 2 rated source.

Wire the DC-input power supply to the terminal base unit as shown in

Figure 10

.

Figure 10 - DC Input Power Supply Connections

Connect the Relay

The XM-124 module has Normally Open relay contacts, which close when the
control output is energized.

The alarms associated with the relay and whether the relay is normally de-
energized (non-failsafe) or normally energized (failsafe) depends on the
configuration of the module.

Refer to Relay Parameters on page 82

for details.

-

24V dc

Power

Supply

+

-

IMPORTANT

A Class 2 circuit can be provided by use of an NEC Class 2 rated power
supply, or by using a SELV or PELV rated power supply with a 5 A current
limiting fuse installed before the XM module.

IMPORTANT

24V DC needs to be wired to terminal 44 (+24V In) to provide power to the
device and other XM modules linked to the wired terminal base via the side
connector.

ATTENTION: The power connections are different for different XM
modules. Refer to the installation instructions for your specific XM
module for complete wiring information.