INSTALLATION

A1.8

A1.8

VANTAGE® 500

Figure A1.1 Connection of the Vantage® 500 to Premises Wiring

1. Install the double-pole, double-throw switch

between the power company meter and the
premises disconnect.

Switch rating must be the same as or greater than the
customer’s premises disconnect and service over cur-
rent protection.

2. Take necessary steps to assure load is limited to

the capacity of the Vantage by installing a 50 amp,
240 VAC double-pole circuit breaker. Maximum
rated load for each leg of the 240 VAC auxiliary is
50 amperes. Loading above the rated output will
reduce output voltage below the allow-

able -10% of rated voltage, which may damage
appliances or other motor-driven equipment and
may result in overheating of the Vantage 500
engine.

3. Install a 50 amp 120/240 VAC plug (NEMA Type

14-50) to the double-pole circuit breaker using
four-conductor cable of the proper size and desired
length. (The 50 amp, 120/240 VAC plug is avail-
able in the optional K802R plug kit.)

4. Plug this cable into the 50 amp 120/240 volt recep-

tacle on the Vantage 500 case front.

240 Volt

60 Hz.

3-Wire

Service

POWER

COMPANY

METER

240 VOLT

120 VOLT

120 VOLT

LOAD

N

NEUTRAL
BUS

GROUND

PREMISES

DISCONNECT AND

SERVICE

OVERCURRENT

PROTECTION

GND

N

4 CONDUCTOR COPPER CABLE

SEE NATIONAL ELECTRICAL CODE FOR

WIRE SIZE RECOMMENDATIONS.

240 VOLT

GROUNDED CONDUCTOR

50AMP

240 VOLT

DOUBLE

POLE

CIRCUIT

BREAKER

DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES

SERVICE OVERCURRENT

PROTECTION.

50 AMP, 120/240

VOLT PLUG

NEMA TYPE 14-50

50 AMP, 120/240 VOLT

RECEPTACLE