Rockwell Automation Publication 1756-UM020I-EN-P - August 2012

83

Add, Configure, Monitor, and Replace CIP Safety I/O

Chapter 5

7. Click

to the right of the safety network number to open the Safety

Network Number dialog box.

8. Click Set.

9. Verify that the Network Status (NS) status indicator is alternating

red/green on the correct module before clicking Yes on the confirmation
dialog box to set the SNN and accept the replacement module.

10. Follow your company-prescribed procedures to functionally test the

replaced I/O module and system and to authorize the system for use.