Access faultrecord attributes – Rockwell Automation 1756-SPESMNRMXT GuardLogix Controllers User Manual Manuel d'utilisation

Page 133

Advertising
background image

Rockwell Automation Publication 1756-UM020I-EN-P - August 2012

133

Monitor Status and Handle Faults

Chapter 9

Access FaultRecord Attributes

Create a user-defined structure to simplify access to the MajorFaultRecord and
SafetyTaskFaultRecord attributes.

For more information on using the GSV and SSV instructions, refer to the Input/
Output Instructions chapter of the Logix5000 Controllers General Instructions
Reference Manual, publication

1756-RM003

.

Safety
Controller

SafetyLocked

SINT

Indicates whether the controller is safety-locked or -unlocked.

SafetyStatus

(2)

INT

Specifies the safety status as the following:

Safety task OK. (1000000000000000)
Safety task inoperable. (1000000000000001)
Partner missing. (00000000000000000)
Partner unavailable. (00000000000000001)
Hardware incompatible. (00000000000000010)
Firmware incompatible. (00000000000000011)

SafetySignatureExists

SINT

Indicates whether the safety task signature is present.

SafetySignatureID

DINT

32-bit identification number.

SafetySignature

String

(3)

32-bit identification number.

SafetyTaskFaultRecord

(1)(2)

DINT[11]

Records safety task faults.

AOI (Safety)

LastEditDate

LINT

Date and time stamp of the last edit to an Add-On Instruction
definition.

SignatureID

DINT

ID number.

SafetySignatureID

DINT

32-bit identification number.

(1) See

Access FaultRecord Attributes on page 133

for information on how to access this attribute.

(2) See

Capture Fault Information on page 134

for information on how to access this attribute.

(3) Length = 37.
(4) From the standard task, GSV accessibility of safety object attributes is the same as for standard object attributes.

Table 42 - GSV/SSV Accessibility

Safety
Object

Attribute Name

Data Type

Attribute Description

Accessible from

the Safety Task

Accessible from

Standard Tasks

GSV

SSV

GSV

(4)

SSV

Table 43 - Parameters for Accessing FaultRecord Attributes

Name

Data Type

Style

Description

TimeLow

DINT

Decimal

Lower 32 bits of the fault timestamp value

TimeHigh

DINT

Decimal

Upper 32 bits of the fault timestamp value

Type

INT

Decimal

Fault type (program, I/O, or other)

Code

INT

Decimal

Unique code for this fault (dependent on fault type)

Info

DINT[8]

Hexadecimal

Fault-specific information (dependent on fault type and
code)