Chapter 4

Communicate over Networks

Change the Safety Network Number (SNN) of the Controller

1. In the Controller Organizer, right-click the controller and choose

Properties.

2. On the General tab of the Controller Properties dialog box, click

to

the right of the safety network number to open the Safety Network
Number dialog box.

3. Click Time-based and then Generate.

4. Click OK.

Change the Safety Network Number (SNN) of Safety I/O Modules on the CIP Safety Network