20

Rockwell Automation Publication 1756-UM020I-EN-P - August 2012

Chapter 1

System Overview

Selecting Safety I/O Modules

Safety input and output devices can be connected to CIP Safety I/O on
DeviceNet or EtherNet/IP networks, allowing output devices to be controlled by
a GuardLogix controller system via DeviceNet or EtherNet/IP communication.

For the most up-to-date information on available CIP Safety I/O catalog
numbers, certified series, and firmware revisions, see

http://www.ab.com/certification/safety

.

Selecting Communication
Networks

The GuardLogix controller supports communication that lets it do the
following:

Distribute and control Safety I/O on DeviceNet or EtherNet/IP

networks.

Distribute and control remote Safety I/O on DeviceNet, EtherNet/IP, or

ControlNet networks.

Produce and consume safety tag data between 1756 and 1768 GuardLogix

controllers across EtherNet/IP or ControlNet networks or within the
same ControlLogix chassis.

Distribute and control standard I/O on EtherNet, ControlNet, or

DeviceNet networks.

Use these communication modules to provide an interface between GuardLogix
controllers and network devices.

The GuardLogix controller can connect to RSLogix 5000 programming software
via a serial or USB connection, an EtherNet module, or a ControlNet module.

1756-L6

xS controllers have a serial port. 1756-L7xS controllers have a USB port.

See the

Additional Resources on page 13

for more information on using network

communication modules.

Table 6 - Communication Modules

To interface between

Use this module

Refer to these
Installation
Instructions

The GuardLogix controller and DeviceNet devices

1756-DNB

DNET-IN001

The GuardLogix controller and EtherNet/IP devices

1756-ENBT
1756-EN2T
1756-EN2F
1756-EN2TR, 1756-EN3TR
1756-EN2TXT

ENET-IN002

Controllers on the ControlNet network

1756-CN2, 1756-CN2R
1756-CN2RXT

CNET-IN005