Install an Energy Storage
Module (ESM)

To install an ESM, complete these steps. Follow the same steps for the safety
partner.

1. Align the tongue-and-groove slots of the ESM and controller.

2. Slide the ESM into the chassis until it snaps into place.

The ESM begins charging after installation. Charging status is indicated by one
of these status messages:

ESM Charging
CHRG

After you install the ESM, it may take up to 15 seconds for the charging status
messages to display.

Table 10 - Compatible Energy Storage Modules

Cat. No.

Compatible ESMs

1756-L7xS

1756-ESMCAP, 1756-ESMNSE, 1756-ESMNRM

1756-L7xSXT

1756-ESMCAPXT, 1756-ESMNSEXT, 1756-ESMNRMXT

1756-L7SP

1756-SPESMNSE, 1756-SPESMNRM

1756-L7SPXT

1756-SPESMNSEXT, 1756-SPESMNRMXT

ATTENTION: To avoid potential damage to the product when inserting the ESM,
align the ESM in the track and slide forward with minimal force until the ESM
snaps into place.

IMPORTANT

Allow the ESM to finish charging before removing power from the controller. To
verify that the ESM is fully charged, check the status display to confirm that
messages ‘CHRG’ or ‘ESM Charging’ are no longer indicated.

TIP

Check the WallClockTime object attributes after installing an ESM to verify that
time of the controller is correct.

Logix 55xx

RUN FORCESD OK