Chapter 2

Using AutoFlash to Update Firmware

To update your controller firmware with the AutoFlash feature of RSLogix 5000
software, follow these steps.

1. Verify that the appropriate network connection is made and your network

driver is configured in RSLinx software.

2. Use RSLogix 5000 programming software to create a controller project at

the version you need.

3. Click RSWho to specify the controller path.

4. Select your controller and click Update Firmware.

5. Select the firmware revision to update to.

6. Click Update.

7. Click Yes.

Allow the firmware update to complete without interruption. When the
firmware upgrade is complete, the Who Active dialog box opens. You may
complete other tasks in RSLogix 5000 software.