If the controller is faulted, these messages may be indicated on the status display.

Major Recoverable Fault Messages

Major recoverable faults are indicated by Major Fault T

XX:CXX message on the

controller status display.

Table 50 on page 140

lists specific fault types, codes, and

the associated messages as they are shown on the status display.

For detailed descriptions and suggested recovery methods for major recoverable
faults, see the Logix5000 Major, Minor, and I/O Fault Codes Programming
Manual, publication 1756-PM014.

Table 49 - Fault Messages

(1)

Message

Interpretation

Major Fault TXX:CXX message

A major fault of Type XX and Code XX has been detected.
For example, if the status display indicates Major Fault T04:C42 Invalid JMP Target, then a JMP instruction is programmed to jump to an
invalid LBL instruction.

I/O Fault Local:X #XXXX message

An I/O fault has occurred on a module in the local chassis. The slot number and fault code are indicated along with a brief description.
For example, I/O Fault Local:3 #0107 Connection Not Found indicates that a connection to the local I/O module in slot three is not open.
Take corrective action specific to the type of fault indicated.

I/O Fault ModuleName #XXXX message

An I/O fault has occurred on a module in a remote chassis. The name of the faulted module, as configured in the I/O Configuration tree of
RSLogix 5000 software, is indicated with the fault code and brief description of the fault.
For example, I/O Fault My_Module #0107 Connection Not Found indicates that a connection to the module named ’My_Module’ is not
open.
Take corrective action specific to the type of fault indicated.

I/O Fault ModuleParent:X #XXXX message

An I/O fault has occurred on a module in a remote chassis. The module’s parent name is indicated because no module name is configured in
the I/O Configuration tree of RSLogix 5000 software. In addition, the fault code is indicated with a brief description of the fault.
For example, I/O Fault My_CNet:3 #0107 Connection Not Found indicates that a connection to a module in slot 3 of the chassis with the
communication module named ’My_CNet’ is not open.
Take corrective action specific to the type of fault indicated.

X I/O Faults

I/O faults are present and X = the number of I/O faults present.
In the event of multiple I/O faults, the controller indicates the first fault reported. As each I/O fault is resolved, the number of faults
indicated decreases and the next fault reported is indicated by the I/O Fault message.
Take corrective action specific to the type of fault indicated.