After bat indicator turns on – Rockwell Automation 1756-SPESMNRMXT GuardLogix Controllers User Manual Manuel d'utilisation

Page 144

Advertising
background image

144

Rockwell Automation Publication 1756-UM020I-EN-P - August 2012

Appendix B

Maintain the Battery

After BAT Indicator Turns On

IMPORTANT

If the BAT indicator turns on for the first time when you apply power to the
controller, the battery life is less than

Table 53

indicates. There is always a

small constant drain on the battery. Some of the battery life may have been
used while the controller was off and unable to turn on the BAT indicator.

Table 53 - Battery Life After the BAT Indicator Turns Red (worst-case)

Temperature, Max.
25.4 mm (1 in.) Below the Chassis

Power Cycles

Project Size

1 MB

2 MB

4 MB

8 MB

0…20 °C (0…68 °F)

3 per day

26 weeks

18 weeks

12 weeks

9 weeks

1 per day

26 weeks

26 weeks

26 weeks

22 weeks

1 per month

26 weeks

26 weeks

26 weeks

26 weeks

21…40 °C (70…104 °F)

3 per day

18 weeks

14 weeks

10 weeks

8 weeks

1 per day

24 weeks

21 weeks

18 weeks

16 weeks

1 per month

26 weeks

26 weeks

26 weeks

26 weeks

41…45 °C (106…113 °F)

3 per day

12 weeks

10 weeks

7 weeks

6 weeks

1 per day

15 weeks

14 weeks

12 weeks

11 weeks

1 per month

17 weeks

17 weeks

17 weeks

17 weeks

46…50 °C (115…122 °F)

3 per day

10 weeks

8 weeks

6 weeks

6 weeks

1 per day

12 weeks

11 weeks

10 weeks

9 weeks

1 per month

12 weeks

12 weeks

12 weeks

12 weeks

51…55 °C (124…131 °F)

3 per day

7 weeks

6 weeks

5 weeks

4 weeks

1 per day

8 weeks

8 weeks

7 weeks

7 weeks

1 per month

8 weeks

8 weeks

8 weeks

8 weeks

56…60 °C (133…140 °F)

3 per day

5 weeks

5 weeks

4 weeks

4 weeks

1 per day

6 weeks

6 weeks

5 weeks

5 weeks

1 per month

6 weeks

6 weeks

6 weeks

6 weeks

Advertising