GE Industrial Solutions AKD-20 Low Voltage Switchgear Manuel d'utilisation

Page 55

Advertising
background image

AKD-20 Low-voltage Switchgear

Chapter 7. Operating the Switchgear

55

©2012 General Electric All Rights Reserved

Padlocking the Shutter (See Fig. 7-8)

1. Shutter locking rod

2. Shutter padlock tab

Fig. 7-8. Shutter padlocking

The shutter on each cubicle can be padlocked to prevent access

to the live primary conductors. The shutter can be padlocked

without the breaker installed. One padlock can be placed on a

cassette. To padlock shutter, pull out the shutter locking tab and

insert padlock, see Fig 7-8. Pulling out the shutter locking tab

actuates a rod (1) that goes through stationary and moving

shutter parts that prevents it from opening.

Removing Entelliguard G Shutter Units (on a de-
engergized cubicle)

Visual inspection of primary stab tips can be made by first

removing the breaker and opening the shutters manually. This is

done by rotating the actuating lever that opens the shutter (See

Fig. 7-9). If it is necessary to perform work on the primary

disconnects, the shutter unit and the stab tip bracing must be

removed. To remove the shutter, remove the four screws in the

corners of the shutter and carefully remove shutter unit.

WARNING: Unless the proper precautions are taken, the

removal of a shutter unit presents the hazard of electrical

shock and burn. Do not remove the shutter unit unless the

equipment has been de-energized. Failure to do this can result

in serious injury.

ADVERTISSEMENT

:

A moins que les précautions nécessaires ne

soient prises, l’installation d’une unité à volet présente des

risques de choc électrique ou de brûlure. Il ne faut pas installer

l’unité à volet à moins que l’équipement ait été désamorcé.

L’omission de ce faire peut résulter en blessures sérieuses.

To remove these shutter units, proceed as follows:

1. The shutter is mounted by four screws on the horizontal stab

tip braces located at each side of the rear of the breaker

compartment. See Fig. 7-9.

2. Take out two slotted head screws on each side of the

frame and carefully remove the shutter unit.


3. Carefully remove the entire shutter frame.


4. The frame is then maneuvered forward past the racking

cams on each side, then upward and forward out of the

cassette.

1

Shutter

actuating

lever

Fig. 7-9 Envelope 1 &

Envelope 2 shutter assembly

2

Advertising