EntelliGuard G Short Circuit and Interrupting Ratings: ANSI/UL1066

Interrupting Rating Tier ANSI/UL1066 Devices, LVPCB

Envelope 1

Envelope 2

Envelope 3

Type

240 V

480 V

600 V

1/2S Withstand

400 to 2000

3200

400 to 3200

3200

4000 to 5000

S

65,000

65,000

50,000

50,000

X

N

65,000

65,000

65,000

65,000

X

X

H

85,000

85,000

65,000

65,000

X

P

100,000 100,000

65,000

65,000

X

E

85,000

85,000

85,000

85,000

X

M

100,000 100,000

85,000

85,000

X

X

B

100,000 100,000

100,000

100,000

X

X

L

150,000 150,000

100,000

100,000

X

X

Table 3.-2. Breaker interrupting rating

Fig. 3-12. EntelliGuard G Breaker

Envelope 1 EntelliGuard G Circuit Breaker

2000-ampere frame size

Up to 85 kAIC interrupting rating

Four-high stacking, 22-inch wide sections

Envelope 2 EntelliGuard G Circuit Breaker

2000-ampere frame size

Up to 100 kAIC interrupting rating

Four-high stacking, 22-inch wide sections

Envelope 2 EntelliGuard G Circuit Breaker

3200-ampere frame size

Up to 100 kAIC interrupting rating

Available in 30 inch wide sections

Envelope 3 EntelliGuard G Circuit Breaker

4000-ampere frame size

Up to 100 kAIC interrupting rating

Available in 38 inch wide sections

3-8 Compartments for Future

Breakers

When specified, compartments may be supplied for future
addition of circuit breaker elements. These compartments are
fully equipped with drawout rails, primary disconnects, and
ancillary devices as required (i.e. secondary disconnects,
accessory devices, etc.) The opening in the breaker
compartment door (3), Fig. 3-14, is closed with a bolted-on steel

plate (2) to deter accidental contact with energized electrical
circuits.(i.e. primary disconnect stabs).

1.

Quarter-turn latch

2.

Steel plate (future breaker cubicle)

Fig. 3-13. Future Compartment

3. Future cubicle door cover

Fig. 3-14. Future breaker compartment cover (padlockable

¼ turn latch will be provided on future breaker cubicles)

3

1

2

Advertising