Power cable connections, Relays and control devices – GE Industrial Solutions AKD-20 Low Voltage Switchgear Manuel d'utilisation

Page 43

Advertising
background image

AKD-20 Low Voltage Switchgear
Chapter 4. Equipment Installation

43

©2012 General Electric All Rights Reserved

Equipment

Depth “A”

Direction

of Leads

B

60” Below 19

Above

24

67” Below 26

Above

31

74” Below 33

Above

38

Table 4.23 Floor Plan


Power Cable Connections

Connect the main cables to the main lugs. Before any main

cable connections are made, the cables should be identified to

indicate their phase relationship with the equipment. Adequate

electrical and mechanical clearances must be provided between

conduit, cables, and bus. Where the cables enter the section,

they can be lashed to optional cable supports at the rear of the

cable compartment as required.

Mechanical cable terminals are normally included with the

switchgear (compression terminals are supplied when ordered)

and are mounted at the ends of the breaker runbacks in the

cable compartment. Carefully follow the cable manufacturer's

recommendations for installation of cable.

Install the cables in the proper path to the terminals, using

temporary lashing if required. Cut the cables to the proper

length. Strip the insulation to the desired dimension, being

careful not to damage any strands.

For copper cables, coat the wires with GE lubricating grease

D6A15A2, insert the cables into the terminals, and tighten the

set screws in accordance with torque values shown in the

torque value table for cable terminals in the addendum of this

manual. See Appendix A, Table A-3.

For aluminum cables, wire brush the wire strands thoroughly.

Immediately after wire brushing, coat the cable strands with a

quality oxide inhibiting compound such as Penetrox A. Insert

exposed wires into the terminals and tighten the set screws in

accordance with values shown in the torque Table A-3 in

Appendix A of this Instruction Book

.

CAUTION: The torque values shown in the table are for dry

threads only. Do not grease or otherwise lubricate the

threads on the cable terminals as this will permit over-

tightening of the screw and possible damage to the terminal

or cable.

ATTENTION: Les valeurs de couple indiquées dans le tableau

ne sont valables que pour des filets secs uniquement. Il ne

faut pas graisser ou librifier autrement les filets des câbles

terminaux, car cela produira un serrage excessif de la vis et

possiblement des dommages au terminal ou au câble.

This should result in the oozing of compound material from

between individual strands. Wipe off any excess compound.

Bolt the cable terminal connectors to the ends of the bars in the

cable compartment. A non-oxidizing grease, such as GE

lubricating grease D6A15A2 furnished with each equipment,

should be used at these connection surfaces. The bolts should

be tightened in accordance with values shown in the torque

Table A-3 in Appendix A of this Instruction Book

Lash the cables securely to the cable support, if present, to take

their weight off the runbacks and to brace them against short

circuit forces in the event of a fault.

Fig. 4-24. Typical cable lashing

The cable supports in fig. 4-24 can be optionally ordered from

the factory. The following instructions for cable lashing should

be used as a guide. Run and bend the main cable in a most

convenient orientation, making sure the main cable has been

located directly up against any cable braces (if present) before it

connects to the main cable terminals. Using a 3/8 inch diameter

continuous nylon rope or equivalent (minimum 2000 pounds

tensile strength) at 6 inches from the main cable terminals,

make five revolutions around the "A" and "B" phase main cables,

making sure the rope does not overlap. Make five revolutions

around the "B" and "C" phase main cables. With the remaining

rope, wrap around the main cable lashing between the "B" and

"C" phase and the cable brace (if present) with a minimum of 5

revolutions getting as much revolutions as possible between the

phases. Continue wrapping between the "A" and "B" phase

around the main cable lashing and the cable brace (if present)

with a minimum of 5 revolutions getting as much revolutions as

possible between the phases. Securely tie off the remaining

rope. Repeat this lashing at every 6-inch interval.

Relays and Control Devices

Remove all blocking on relays and devices as shown in the

instructions accompanying the devices.

Nylon rope – 3/8

inch (9.5 mm)

diameter.

Minimum of 5

wraps

6 inches

(152 mm)

Advertising