GE Industrial Solutions AKD-20 Low Voltage Switchgear Manuel d'utilisation

Page 51

Advertising
background image

AKD-20 Low-voltage Switchgear

Chapter

6.

Testing

and

Inspection

51

©2012 General Electric All Rights Reserved

All components, except the Neutral Sensor, are integrally mounted

in the circuit breaker. When used, the Neutral Sensor is separately

mounted in the bus or cable compartment of the switchgear. In

drawout construction, it is automatically connected to the trip unit

in the breaker via a drawout secondary disconnect block.

CAUTION: Never disengage the trip unit on a breaker that is

energized and carrying load current. This will open-circuit the

current sensors, allowing dangerous and damaging voltages to

develop.

ATTENTION: Il ne faut jamais désengager le déclencheur d’un

disjoncteur qui est sous tension et transporte un courant de

charge. Cela ouvrira les circuits des détecteurs de courant,

permettant le développement de voltages dangereux et

dommageables.

Complete Instructions for testing the trip units are included with

the test set. The trip unit users manuals are DEH-4567

(Entelliguard trip unit) and DEH-4568 (GTUTK20).

6-5 Final Steps to Be Taken Before
Energizing Equipment

The following steps should be taken before energizing the

equipment:

1. Manually exercise all switches, circuit breakers, and other

operating mechanisms to make certain they are properly

aligned and operate freely.


2. Conduct an electrical insulation resistance test to make sure

the switchgear is free from short circuits and grounds. This

should be done both phase-to-ground and phase-to-phase

with the switches or circuit breakers both opened and

closed. This test should be performed with a 1000 volt

meggar. Disconnect all control circuits before checking

resistance.

3. Check any electrical relays, meters, or instrumentation to

determine that connections are made properly and the

devices function properly.


4. Electrically exercise all electrically operated circuit breakers,

and other mechanisms (but not under load), to determine

that the devices operate properly. An auxiliary source of

control power may be necessary to provide power to the

electrical operators.


5. Test the ground fault protection system (if furnished) in

accordance with the manufacturer's instructions.


6. Set the adjustable current and voltage trip mechanisms to

the proper values. Experience has indicated that damage

from faults can be reduced if the devices used for overload

and short circuit protection are set to operate

instantaneously (that is, without intentional time delay) at

115 percent of the highest value of phase current which is

likely to occur as the result of any anticipated motor starting

or welding currents.

7. Make certain that field wiring is clear of live bus and, where

necessary, physically secured to withstand the effects of

fault currents.


8. Check to determine that all grounding connections are

made properly.

9. Remove all debris, scrap wire, etc., from the switchgear

interior before closing the enclosure.

10. Install covers, close doors, and make certain that no wires

are pinched and that all enclosure parts are properly

aligned and tightened.

Advertising