11 feeder cable and busway compartment – GE Industrial Solutions AKD-20 Low Voltage Switchgear Manuel d'utilisation

Page 24

Advertising
background image

AKD-20 Low Voltage Switchgear
Chapter 3. Description

24

©2012 General Electric All Rights Reserved

Insulation and isolation of the vertical riser bus bars (1), Fig. 3-23, is

provided by installing phase isolation barriers (not shown) between

the bus bars and by mounting covers (4) over the bus bars.

The phase isolation barriers and riser bus covers are constructed

from insulating material. Insulation of the horizontal main bus bars

(2) is achieved by an oven cured coating of epoxy.

The vertical/ horizontal bus bar joints are covered with collars (3)

and caps (4) held in place with nylon thumb screws (5). The collars

and caps are constructed from insulating material.

1.

Molded

base

2. Vertical riser buses (cover removed to show bus

location)

3. Vertical bus bracing.

4. Run In conductors.

5. Insulated run backs

Fig. 3-22. Bus system

Figure 3-22 illustrates the various components comprising the

vertical main bus bars (2). Bus bars are supported by molded or

machined barriers, (1). Vertical bus can be braced (3) depending on

the interrupting rating of the switchgear. Conductors that provide

current to the breaker compartments are called run in bars (4) and

are bolted to the riser bus bars. Insulated run back bars (5) are for

connecting load conductor cabling.

1. Vertical bus barrier

2. Insulated bus bar (epoxy coated)

3.

Joint

collars

4. Joint

caps

5. Nylon thumb screws

Fig. 3-23. Insul-bar horizontal bus insulation system

3-11 Feeder Cable and Busway
Compartment

The rear cable and terminal compartment, Fig. 3-24, provides for

cable installation and terminations. The cable bending space meets

the requirements of the National Electric Code. Various

arrangements of single or double cable terminals are provided,

depending upon the purchaser's requirements.

When specified, racks for the support of feeder cables are located in

the cable compartment. The actual support of the cables is

provided by lashing them to these racks.

Also located in the cable compartments are provisions for

terminating control wires between external devices and control

circuits within the switchgear equipments. Figure 3-25 shows this

typical arrangement.

2

1

5

2

3

4

5

1

4

3

Advertising