AKD-20 Low Voltage Switchgear
Chapter 3. Description

25

©2012 General Electric All Rights Reserved

1. Cable lugs - mechanical type

Fig. 3-24. Cable termination provisions

See Fig. 3-25. When furnished, the terminal boards (2), Fig. 3-25, for

such connections are located in an enclosed vertical wiring trough

mounted on the side of the cable compartment. The trough is of

steel construction with bolted covers to provide an isolation barrier

between the control wiring (1) and the adjacent power cables.

A neutral bus, insulated from ground, is provided in the bus area on

switchgear designed for four-wire systems. The neutral bus is

located near the top of the cable compartment. It includes

provisions for terminating the neutral conductor of four-wire feeder

cables and also direct mounting of the neutral CT or neutral

Rogowski as required for those feeder system circuit breakers

having a ground fault trip function.

1.

Internal

equipment control wiring

2.

Terminal

boards

3. Space for purchaser's field control wiring

Fig. 3-25. Control wiring termination trough


3-12 Ground Bus

All General Electric AKD-20 switchgear sections are grounded to the

internal equipment ground bus (4), Fig. 3-26, located at the bottom

of the cable compartment.

1

2

3