Interstitial space is tested continuously.

Vacuum source is the submerged turbine pump siphon port.

Presence of a water table above the leak point will allow water to enter the interstice rather than air or vapor.

The water would be detected in the same manner as fuel.

This system may not be compatible with all secondarily contained tanks and/or piping. Always consult with the

tank and/or piping manufacturer and the manufacturer’s applicable recommended installation practices before

installing this system, or damage may be caused to the tank or piping by its use.

Franklin Fueling Systems

Evaluator: Ken Wilcox Associates

3760 Marsh Road

Tel: (816) 443-2494

Madison, WI 53718

Date of Evaluation: 11/11/04

Tel: (800) 225-9787

E-mail: [email protected]

URL: www.franklinfueling.com

|

Home

|

Vendors: A - F

|

Vendors: G - M

|

Vendors: N - S

|

Vendors: T - Z

|

Method Index

|

Glossary

|

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the

performance of the method or equipment.

Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to

our expanded "

DISCLAIMER

" page.

Page 2 of 2

Franklin Fueling Systems B

2/28/2007

http://www.nwglde.org/evals/franklin_fueling_b.html

Extrait du site Web du groupe de travail américain NWGLDE (National Work Group on Leak Detection Evaluations). 20 février 2007.
<http://www.nwglde.org/evals/franklin_fueling_e.html>