Error fl ags, Cause what to do, 0). n.b.: with hysteresis less than “0 – Celduc Temperature controller ECOM Manuel d'utilisation

Page 69: 0) dotted line moves under the alarm setpoint

Advertising
background image

70

ECOM0010 - User manual

Pv

Comand Spv

Alarm Spv

Off

On

On

Hysteresis

parameter

$+< > 0

Time

Alarm

output

Comand Spv

Comand Spv

Comand Spv

Comand Spv

Alarm Spv

Alarm Spv

Value of alarm setpoint less
than “0” and hysteresis value
greater than “0” (Par.20

D+<

> 0).
N.B.: With hysteresis less
than “0” (

D+<

< 0) dotted

line moves under the alarm
setpoint.

10

Error fl ags

If the system shows malfunctions, the controller switches off
the control output and reports the error fl ags on word 1009.
For example, the controller will report a defective
thermocouple by fl ashing alternately red/yellow LED and
setting to 1 the bit 0 of the word 1009.
For other signals see table below:

Cause

What to do

BIT2

Error programming the
EEPROM

Call assistance

BIT0

Cold junction sensor
failure or room
temperature OFF the
limits

Call assistance

BIT3

Incorrect confi guration
data. Possible loss of
calibration values

Check that confi guration
parameters are correct

BIT1

Broken thermocouple
or temperature OFF the
limits

Check the connection
with the sensors and their
integrity

BIT4

Missing calibration

Call assistance