User manual - ECOM0010

55

Modbus

address

Description

Read

Write

Reset

value

0

Type of device

RO EEPROM

1

Software version

RO EEPROM

5

Slave address

R/W EEPROM

50

Automatic addressing

WO

-

51

System code comparison

WO

-

500

Restore default values (write 9999)

RW

0

1000 Process (tenth of degree)

RO

?

1001

Control setpoint (measure to the tenth
of degree)

R/W EEPROM

1002

Alarm 1 setpoint (tenth of degree)

R/W EEPROM

1003

Start/Stop
0=controller in STOP
1=controller in START

R/W

0

1004

With automatic tuning (word 2005 = 1):
0=autotuning function OFF
1=autotuning function ON

RO

0

With manual tuning (word 2005 = 2):
0=autotuning function OFF
1=autotuning funciton ON

R/W

0

With synchronized tuning (word 2005 = 3):
0=autotuning function OFF
1=control output OFF (forces control
cooling)
2=control output ON (forces control
heating)
3=autotuning ON
4=autotuning completed

R/W

0

1005

Automatic/manual selection
0=automatic ; 1=manual

R/W

0

1006

Output status (0=off, 1=on)
Bit 0 = OUT1

Bit 1 = OUT2

RO

0