ECOM0010 - User manual

18

D/

Alarm 1 selection.

The alarm is related to AL1.
Word modbus 2018
0

Disabled. > Default.

1

Absolute alarm, referring to measurement
(process)

2

Alarm band



6QQFSEFWJBUJPOBMBSN

4

Lower deviation alarm

5

Absolute alarm, referring to setpoint

6

Alarm status (active in Run / Start)

7

Cooling output

8

Heater Break Alarm

9

Loop Break Alarm

10

Copy of OUT1

19

DVR

Alarm 1 State Output

Alarm 1 output contact and type of action
Word modbus 2019
0

Normally open, active from start. > Default.

1

Normally closed, active from start

2

Normally open, active from alarm reaching

1



/PSNBMMZDMPTFE BDUJWFGSPNBMBSNSFBDIJOH

2

20

D+\

Alarm 1 Hysteresis

Word modbus 2020

LabSoftView:
-99.9..+99.9 degrees >
Default: 0
E.g. : 1 = 1 °C / °F

Modbus:
-999..+999 tenths of
degrees
E.g. : 10 = 1.0 °C / °F

2

At starting, the output is inhibited if the device is in alarm condition. It is
activated at each alarm start.