Celduc Temperature controller ECOM Manuel d'utilisation

Page 58

Advertising
background image

User manual - ECOM0010

59

6

VGWX

Setpoint Deviation Tuning

Selects deviation from control setpoint as threshold used
by manual tuning to calculate PID parameters
Word modbus 2006

LabSoftView:
0..50.0 degrees >
Default: 20.0
E.g. : 20 = 20 °C / °F

Modbus:
0..500 tenths of degrees
E.g. : 200 = 20 °C / °F

7

P*WX

Max Gap Tuning

Selects the max. process-setpoint gap above which the
automatic tuning recalculates PID parameters
Word modbus 2007

LabSoftView:
0.1..50.0 degrees > Default: 1
E.g. : 10 = 10 °C / °F

Modbus:
1..500 tenths of degrees
E.g. : 10 = 1.0 °C / °F

8

PQSE

Minimum Proportional Band

Selects the min. proportional band value selectable by the
automatic tuning
Word modbus 2008

LabSoftView:
0..100.0 degrees > Default: 5
E.g. : 5 = 5 °C / °F

Modbus:
0..1000 tenths of degrees
E.g. : 50 = 5.0 °C / °F

9

PDSE

Maximum Proportional Band

Selects the max. proportional band value selectable by the
automatic tuning
Word modbus 2009

LabSoftView:
EFHSFFTDefault: 50
E.g. : 50 = 50 °C / °F

Modbus:
UFOUITPGEFHSFFT
E.g. : 500 = 50.0 °C / °F