Celduc Temperature controller ECOM Manuel d'utilisation
Page 58
User manual - ECOM0010
59
6
VGWX
Setpoint Deviation Tuning
Selects deviation from control setpoint as threshold used
by manual tuning to calculate PID parameters
Word modbus 2006
LabSoftView:
0..50.0 degrees >
Default: 20.0
E.g. : 20 = 20 °C / °F
Modbus:
0..500 tenths of degrees
E.g. : 200 = 20 °C / °F
7
P*WX
Max Gap Tuning
Selects the max. process-setpoint gap above which the
automatic tuning recalculates PID parameters
Word modbus 2007
LabSoftView:
0.1..50.0 degrees > Default: 1
E.g. : 10 = 10 °C / °F
Modbus:
1..500 tenths of degrees
E.g. : 10 = 1.0 °C / °F
8
PQSE
Minimum Proportional Band
Selects the min. proportional band value selectable by the
automatic tuning
Word modbus 2008
LabSoftView:
0..100.0 degrees > Default: 5
E.g. : 5 = 5 °C / °F
Modbus:
0..1000 tenths of degrees
E.g. : 50 = 5.0 °C / °F
9
PDSE
Maximum Proportional Band
Selects the max. proportional band value selectable by the
automatic tuning
Word modbus 2009
LabSoftView:
EFHSFFTDefault: 50
E.g. : 50 = 50 °C / °F
Modbus:
UFOUITPGEFHSFFT
E.g. : 500 = 50.0 °C / °F