ECOM0010 - User manual

10

PQLW

Minimum Integral Time

Selects the min. integral time value selectable by the
automatic tuning
Word modbus 2010
0..9999 tenths of seconds. > Default: 100
E.g.: 100 = 10.0 seconds

11

SE

Proportional Band

Process inertia in units (Ex: if temperature in °C)
Word modbus 2011

LabSoftView:
Default: 0
E.g. : 10 = 10

Modbus:
UFOUIT
E.g. : 10 = 1.0

0 = ON/OFF if also

WL

is equal to 0.

12

WL

Integral Time

Process inertia in seconds
Word modbus 2012 - 0 = Integral action deactivated

LabSoftView:
0..999.9 seconds >
Default: 0
E.g. : 40 = 40 seconds

Modbus:
0..9999 tenths of seconds
E.g. : 400 = 40.0 seconds

0 = Integral action disabled.

13

WG

Derivative Time

Normally ¼ of integral time.
Word modbus 2013 - 0 = Action dérivée désactivée.

LabSoftView:
0..999.9 seconds > Default:
0
E.g. : 10 = 10 seconds

Modbus:
0..9999 tenths of seconds
E.g. : 100 = 10.0 seconds

0 = Derivative action disabled.