ECOM0010 - User manual

25

SEP

Proportional Band Multiplier

Word modbus 2025

LabSoftView:
1 .00..5.00 > Default: 1.00
Ex: 1 = 1

Modbus:
100..500 hundreths
Ex: 100 = 1.00

26

RXGE

Overlap/Dead Band

Dead band combination for heating / cooling PID
Word modbus 2026

LabSoftView:
-20.0..+50.0 % > Default: 0
Ex: 10 = 10 %

Modbus:
-200..+500 tenths of %
Ex: 100 = 10.0 %

Negative: Dead band
Positive: Overlapping

27

FRFW

Cooling Cycle Time

Cycle time for cooling output
Word modbus 2027
TFDPOETDefault: 10

28

DXPD

Aumatic / Manual

Enables the automatic/manual selection
Word modbus 2028
0

Disabled. > Default

1

Enabled

2

Enabled Stored

29

6/DG

Slave Address

Selects slave address for serial communication
Word modbus 2029
1..254. > Default: 240