ECOM0010 - User manual

33

R))/

Off-line

Selects the off-line time. If the communication isn’t availa-
ble within the selected time, the controller will switch off
the control output
Word modbus 2033

LabSoftView:
0..60.0 seconds > Default: 0
E.g. : 10 = 10 seconds

Modbus:
0..600 tenths of seconds
E.g. : 100 = 10.0 seconds

0 = Off-line disable

34

6R)W

Softstart threshold

Selects the threshold under which the device will activate
softstart function at starting
Word modbus 2034

LabSoftView:
-60.0..1000.0 degrees >
Default: 60.0
Ex: 60.0 = 60 degrees

Modbus:
-600..10000 tenths of
degrees
Ex: 100 = 10.0 degrees

35

63(UF

Softstart percentage

Value of the output percentage during softstart
Word modbus 2035
0..100%. >Default: 80%.

36

67LPH

Softstart time

Max. Softstart duration: if the process doesn’t reach the
UISFTIPME FOUFSFE PO QBSBNFUFS  XJUIJO UIF TFMFDUFE
time, the controller will start to regulate on setpoint value
Word modbus 2036
1..1440 minutes > Default: 15