Dxpd – Celduc Temperature controller ECOM Manuel d'utilisation

Page 48

Advertising
background image

User manual - ECOM0010

49

in the system. At this point the autotuning is launched (value
JOXPSE &BDIDPOUSPMMFSDBMDVMBUFTUIFOFX1*%WBMVFT
When the procedure ends, it switches off the control output
and sets the value 4 in word 1004. The master, which keeps
reading the word 1004, checks the various zones and when all
of them have reached the value 4 it will bring to 0 the value
of word 1004.
The various devices will regulate the temperature based on
the new values.
N.B. The master must read the Word 1004 at least every 10
seconds otherwise the controller will automatically exit the
autotuning procedure.

6.4

Automatic / Manual control mode of the

percentage of the output

This function allows to select automatic or manual control of

the output percentage. With parameter 28 (

DXPD

word

2028), you can select two methods.

1. The first selection (write 1 in word 2028) allows to modify,

through the word 1005, the functioning mode: after
writing 1 it is possible to change the output percentage on
word 1011 (range 0-10000).

To return to automatic mode, write 0 on word 1005.
2. The second selection (write 2 in word 2028) enables the

same mode, but with two important variants:

t *G UIFSF JT B UFNQPSBSZ MBDL PG WPMUBHF PS BGUFS TXJUDIPò 

the manual functioning will be maintained as well as the
previously set output percentage value.

t *G UIF TFOTPS CSFBLT EVSJOH BVUPNBUJD GVODUJPOJOH  UIF

controller swithes to manual mode while maintaining the
output percentage control unchanged as generated by
the PID immediately before the break.