User manual - ECOM0010

61

14

WF

Cycle Time

Cycle time (for a switch PID control distance: 10”/ 15”, for
the PID on SSR: 1”) or servo time (declared by the manufac-
turer of the servo-motor)
Word modbus 2014

LabSoftView:
TFDPOET
Default: 1
E.g. : 1 = 1 seconds

Modbus:
UFOUITPGTFDPOET
E.g. : 10 = 1.0 seconds

15

//RS

Lower Limit Output Percentage

Selects min. value for control output percentage.
Word modbus 2015
0..100 % > Default: 0%

16

X/RS

Upper Limit Output Percentage

Selects max. value for control output percentage.
Word modbus 2016
0..100 % > Default: 100%

17

GH*U

Degree

Selects degree type.
Word modbus 2017
0

Centigrades. > Default

1

Fahrenheit.