ECOM0010 - User manual

3

*FD

Gain Calibration AI1

Value in % to multiply with the displayed value and to add
to this displayed value to calibrate the process value
Word modbus 2003

LabSoftView:
-99.9..+99.9 % > Default: 0
E.g. : 10 = 10 %

Modbus:
-999..+999 tenths of %
E.g. : 10 = 1.0 %

The formula is: T

OUT

= T

IN

+ (T

IN

x Gain / 100)

T

IN

: Measure

T

OUT

: Displayed value

4

F+\

Command Hysteresis

Hysteresis on ON/OFF control or dead band in PID.
Word modbus 2004

LabSoftView:
-99.9..+99.9 degrees >
Default:0
E.g. : 10 = 10 °C / °F

Modbus:
-999..+999 tenths of
degrees
E.g. : 10 = 1.0 °C / °F

5

WXQH

Tune

Autotuning type selection.
Word modbus 2005
0

Disabled. > Default.

1

Automatic. Calculation of PID parameters at
starting and on control setpoint modification.

2

Manual. Launch by word modbus 1004.