ECOM0010 - User manual

controllers with the same address on the same line.
Address 255 can be used by the Master to communicate with
all the connected equipment (broadcast mode), while with
the address 0 all the devices receive the command, but no
response is expected.
ECOM0010 can introduce a delay (in milliseconds) of the
response to the master request. This delay must be set on
QBSBNFUFS

6HGH

Each parameter modification is saved by the controller in
the EEPROM memory (100000 writing cycles), while the
setpoints are saved with a delay of 10 seconds after the last
modification.
NB: Changes made to words that are different from those
reported in the following table can lead to malfunction.

Modbus RTU protocol features

Baud-rate

Selectable on parameter 30

EGUW

Value 0: 1200bit/s

Value 5: 28800bit/s

Value 1: 2400bit/s

Value 6: 38400bit/s

Value 2: 4800bit/s

Value 7: 57600bit/s

Value 3: 9600bit/s

Value 8: 115200bit/s

Value 4: 19200bit/s

Format

Selectable on parameter 31

VSS

Value 0: 8N1

Value 3: 8N2

Value 1: 8E1

Value 4: 8E2

Value 2: 8O1

Value 5: 8O2

Supported
functions

WORD READING (max 20 word) (HEX 0x03, HEX 0x04)
SINGLE WORD WRITING (HEX 0x06)
MULTIPLE WORDS WRITING (max 20 word) (HEX 0x10)

RO = Read Only

R/W = Read/Write

WO = Write Only