ECOM0010 - User manual
controllers with the same address on the same line.
Address 255 can be used by the Master to communicate with
all the connected equipment (broadcast mode), while with
the address 0 all the devices receive the command, but no
response is expected.
ECOM0010 can introduce a delay (in milliseconds) of the
response to the master request. This delay must be set on
QBSBNFUFS
6HGH
Each parameter modification is saved by the controller in
the EEPROM memory (100000 writing cycles), while the
setpoints are saved with a delay of 10 seconds after the last
modification.
NB: Changes made to words that are different from those
reported in the following table can lead to malfunction.
Modbus RTU protocol features
Baud-rate
Selectable on parameter 30
EGUW
Value 0: 1200bit/s
Value 5: 28800bit/s
Value 1: 2400bit/s
Value 6: 38400bit/s
Value 2: 4800bit/s
Value 7: 57600bit/s
Value 3: 9600bit/s
Value 8: 115200bit/s
Value 4: 19200bit/s
Format
Selectable on parameter 31
VSS
Value 0: 8N1
Value 3: 8N2
Value 1: 8E1
Value 4: 8E2
Value 2: 8O1
Value 5: 8O2
Supported
functions
WORD READING (max 20 word) (HEX 0x03, HEX 0x04)
SINGLE WORD WRITING (HEX 0x06)
MULTIPLE WORDS WRITING (max 20 word) (HEX 0x10)
RO = Read Only
R/W = Read/Write
WO = Write Only