background image

50 ControlLogix® Controller and Memory Board

Publication

1756-IN101J-EN-P - November 2004

North American Hazardous Location Approval

The following information applies when
operating this equipment in hazardous
locations:

Informations sur l'utilisation de cet équipement
en environnements dangereux:

Products marked "CL I, DIV 2, GP A, B, C, D" are
suitable for use in Class I Division 2 Groups A, B,
C, D, Hazardous Locations and nonhazardous
locations only. Each product is supplied with
markings on the rating nameplate indicating the
hazardous location temperature code. When
combining products within a system, the most
adverse temperature code (lowest "T" number)
may be used to help determine the overall
temperature code of the system. Combinations
of equipment in your system are subject to
investigation by the local Authority Having
Jurisdiction at the time of installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
conviennent qu'à une utilisation en environnements
de Classe I Division 2 Groupes A, B, C, D dangereux et
non dangereux. Chaque produit est livré avec des
marquages sur sa plaque d'identification qui
indiquent le code de température pour les
environnements dangereux. Lorsque plusieurs
produits sont combinés dans un système, le code de
température le plus défavorable (code de température
le plus faible) peut être utilisé pour déterminer le
code de température global du système. Les
combinaisons d'équipements dans le système sont
sujettes à inspection par les autorités locales
qualifiées au moment de l'installation.

WARNING

EXPLOSION HAZARD

• Do not disconnect

equipment unless power
has been removed or the
area is known to be
nonhazardous.

• Do not disconnect

connections to this
equipment unless power
has been removed or the
area is known to be
nonhazardous. Secure any
external connections that
mate to this equipment by
using screws, sliding
latches, threaded
connectors, or other
means provided with this
product.

• Substitution of

components may impair
suitability for Class I,
Division 2.

• If this product contains

batteries, they must only
be changed in an area
known to be
nonhazardous.

AVERTISSEMENT

RISQUE D'EXPLOSION

• Couper le courant ou

s'assurer que
l'environnement est classé
non dangereux avant de
débrancher l'équipement.

• Couper le courant ou

s'assurer que
l'environnement est classé
non dangereux avant de
débrancher les
connecteurs. Fixer tous les
connecteurs externes
reliés à cet équipement à
l'aide de vis, loquets
coulissants, connecteurs
filetés ou autres moyens
fournis avec ce produit.

• La substitution de

composants peut rendre
cet équipement inadapté à
une utilisation en
environnement de Classe I,
Division 2.

• S'assurer que

l'environnement est classé
non dangereux avant de
changer les piles.