Ok indicator – Rockwell Automation 1756-Lx_Mx ControlLogix Controller and Memory Board Installation Instructions Manuel d'utilisation

Page 36

Advertising
background image

36 ControlLogix® Controller and Memory Board

Publication

1756-IN101J-EN-P - November 2004

OK Indicator

Color

Description

Recommended Action

off

No power is applied.

When ready, turn on power
to the controller.

flashing
red

If the controller is:

Then:

a new controller
(just out of the box)

The controller requires a
firmware update.

See “Update the
Controller
” on page 29.

NOT a new
controller
(previously in
operation)

Major fault occurred.

See “Clear a Major Fault”
on page 37.

solid red

The controller detected a non-recoverable fault,
so it cleared the project from memory.

See “Clear a
Non-Recoverable Fault” on
page 38
.

solid
green

The controller is OK

None

flashing
green

The controller is storing or loading a project to or
from nonvolatile memory.

If the controller has a
CompactFlash card, leave
the card in the controller
until the OK LED turns solid
green.

Advertising