44 ControlLogix® Controller and Memory Board

Publication

1756-IN101J-EN-P - November 2004

Specifications - 1784-CF64 Industrial CompactFlash Card

Description

Value

User Available Memory

64M bytes

Nonvolatile Memory

Yes

Weight

14.2 g (0.5 oz).

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

• 0 … 60°C (32 … 140°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):

• -40 … 85°C (-40 … 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating

Damp Heat):

• 5% … 95% noncondensing

Vibration

IEC60068-2-6 (Test Fc, Operating):

• 2g @ 10-500Hz

Operating Shock

IEC60068-2-27 (Test Ea, Unpackaged Shock):

• 30g

Non-Operating Shock

IEC60068-2-27 (Test Ea, Unpackaged Shock):

• 50g

Emissions

CISPR 11:

• Group 1, Class A

ESD Immunity

IEC 61000-4-2:

• 4kV contact discharges

• 8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:

• 10V/m with 1kHz sine-wave 80%AM from 30MHz…2000MHz

• 10V/m with 200Hz 50% Pulse 100%AM at 900Mhz

• 10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz