Check the ok led – Rockwell Automation 1756-Lx_Mx ControlLogix Controller and Memory Board Installation Instructions Manuel d'utilisation

Page 27

Advertising
background image

ControlLogix® Controller and Memory Board 27

Publication

1756-IN101J-EN-P - November 2004

Check the OK LED

1. What color is the OK LED?

2. Is this a ControlLogix5555 controller?

If:

Then:

Actions:

solid green

The controller is OK and its
firmware has been updated.

No further actions are required.
However, the revision of firmware
must be compatible with your
revision of RSLogix 5000 software.

flashing red

The controller is OK but it requires a
firmware update.

Go to “Determine Which Firmware
Revisions to Use” on page 10.

solid red

The memory board of the controller
may not be compatible with the
revision of firmware.

Go to step 2.

If:

Then:

No

The controller is not operational. Contact your Rockwell
Automation representative or local distributor.

Yes

Go to step 3.

42525

OK LED

Advertising