European hazardous location approval – Rockwell Automation 1756-Lx_Mx ControlLogix Controller and Memory Board Installation Instructions Manuel d'utilisation

Page 49

Advertising
background image

ControlLogix® Controller and Memory Board 49

Publication

1756-IN101J-EN-P - November 2004

European Hazardous Location Approval

European Zone 2 Certification (The following applies when the product bears the
EEx Marking)

This equipment is intended for use in potentially explosive atmospheres as defined by
European Union Directive 94/9/EC.

The LCIE (Laboratoire Central des Industries Electriques) certifies that this equipment has
been found to comply with the Essential Health and Safety Requirements relating to the
design and construction of Category 3 equipment intended for use in potentially explosive
atmospheres, given in Annex II to this Directive. The examination and test results are
recorded in confidential report No. 28 682 010.

Compliance with the Essential Health and Safety Requirements has been assured by
compliance with EN 50021.

IMPORTANT

• This equipment is not resistant to sunlight or other sources

of UV radiation.

• The secondary of a current transformer shall not be

open-circuited when applied in Class I, Zone 2 environments.

• Equipment of lesser Enclosure Type Rating must be installed

in an enclosure providing at least IP54 protection when
applied in Class I, Zone 2 environments.

• This equipment shall be used within its specified ratings

defined by Allen-Bradley.

• Provision shall be made to prevent the rated voltage from

being exceeded by transient disturbances of more than 40%
when applied in Class I, Zone 2 environments.