42 ControlLogix® Controller and Memory Board

Publication

1756-IN101J-EN-P - November 2004

The following specifications apply to all ControlLogix controllers:

Description:

Value:

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

• 0° … 60° C (32 … 140° F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):

• -40° … 85° C (-40 … 185° F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating

Damp Heat):

• 5% … 95% noncondensing

Vibration

IEC60068-2-6 (Test Fc, Operating):

• 2g @ 10-500Hz

Operating Shock

IEC60068-2-27 (Test Ea, Unpackaged Shock):

• 30g

Non-Operating Shock

IEC60068-2-27 (Test Ea, Unpackaged Shock):

• 50g

Emissions

CISPR 11:

• Group 1, Class A

ESD Immunity

IEC 61000-4-2:

• 6kV contact discharges

• 8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:

• 10V/m with 1kHz sine-wave 80%AM from 30MHz … 2000MHz

• 10V/m with 200Hz 50% Pulse 100%AM at 900Mhz

• 10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz

EFT/B immunity

IEC 61000-4-4:

• ±4kV at 5kHz on power ports

• ±4kV at 5kHz on communications ports

Surge Transient Immunity

IEC 61000-4-5:

• ±1kV line-line(DM) and ±2kV line-earth(CM) on AC power ports

• ±2kV line-earth(CM) on communications ports

Conducted RF Immunity

IEC 61000-4-6:

• 10Vrms with 1kHz sine-wave 80%AM from 150kHz … 80MHz