ControlLogix® Controller and Memory Board 37

Publication

1756-IN101J-EN-P - November 2004

Clear a Major Fault

1. Go online with RSLogix 5000 software and get the fault code.

2. Determine what to do next:

Fault Type

Fault Code

Action

1

60

A. Clear the fault.

B. Download the project to the controller.

C. Return the controller to the run/remote run mode.

If the problem persists:

A. Before you cycle power to the controller, record the state

of the OK and RS232 LEDs.

B. Contact Rockwell Automation support. See the back of this

publication.

1

61

A. To get diagnostic information about the fault, see

Knowledgebase document A92558072. To get the
document, see the back of this publication.

B. Clear the fault.

C. Download the project to the controller.

D. Return the controller to the run/remote run mode.

none of the
above

none of the
above

A. Clear the fault.

B. Correct the reason for the fault.

C. Return the controller to the run/remote run mode.

1. PROG

2. RUN

3. PROG

To use the keyswitch of the controller to clear a major fault, turn the keyswitch in the
following sequence: