28 ControlLogix® Controller and Memory Board

Publication

1756-IN101J-EN-P - November 2004

3. Did you replace a memory board with a memory board that

has a different catalog number?

For example, did you replace

a 1756-M13 memory board with a 1756-M23 memory board?

4. Re-install the previous memory board.

5. Update the firmware of the controller to a revision that is

compatible with the memory board that you intend to install.
See “Determine Which Firmware Revisions to Use” on
page 10.

6. Install the new memory board.

7. What color is the OK LED?

If:

Then:

No

The controller is not operational. Contact your Rockwell
Automation representative or local distributor.

Yes

Go to step 4.

If:

Then:

solid green

No further actions are required. However, the revision of
firmware must be compatible with your revision of RSLogix 5000
software.

solid red

The controller is not operational. Contact your Rockwell
Automation representative or local distributor.