Homologations, directives et normes – Elmo Rietschle 2FC4...-1CB Manuel d'utilisation

Page 73

Advertising
background image

Homologations, directives et normes

11

© Gardner Denver Deutschland GmbH

73

/

74

05.2014 · 610.00260.50.000

Homologation d'après UL

Required Markings

For installation on industrial machines in accordance with the Standard for Indus-
trial Machinery NFPA79 for recognized components, and NFPA70 for listed com-
ponents, only. Please check the drives’ name plate for further details.

Maximum Ambient Temperature:

Electronic

Adapter

Ambient

INV MA 2 0.37

ADP MA WDM

45°C

INV MA 2 0.55

ADP MA WDM

45°C

INV MA 2 0.75

ADP MA WDM

45°C

INV MA 2 1.1

ADP MA WDM

40°C

INV MA 4 1.5

ADP MA WDM

35°C

INV MB 4 2.2

ADP MA WDM

45°C

INV MB 4 3.0

ADP MA WDM

40°C

INV MB 4 4.0

ADP MA WDM

35°C

INV MC 4 5.5

ADP MC WDM

40°C

INV MC 4 7.5

ADP MC WDM

35°C

For listed parts (NFPA70):

Enclosure intended for use with field-installed conduit hubs, fittings or closure
plates UL approved in accordance to UL514B and CSA certified in accordance to
C22.2 No. 18, environmental Type 1 or higher.

The ANTRIEBSREGLER is for use in Pollution Degree 2 only.

Internal Overload Protection Operates within 60 seconds when reaching 150% of
the Motor Full Load Current.

Suitable for use on a circuit capable of delivering not more than 5kA rms symme-
trical amperes, 480 Volts for INV Mx 4, maximum when protected by fuses.

“Warning” – Use fuses rated 600V/10A for INV Mx 2 only.

“Warning” – Use fuses rated 600V/30A for INV MB 4 only.

“Warning” – Use fuses rated 600V/30A for INV MC 4 only.

Integral solid state short circuit protection does not provide branch circuit protect-
tion. Branch circuit protection must be provided in accordance with the Manufac-
turer Instructions, National Electrical Code and any additional local codes.

All wiring terminals marked to indicate proper connections for the power supply,
load and control circuitry.

The tightening, torque to connect the motor terminals, is 26,55 lb/in and 5,31 lb/in
to connect the PTC.

Instruction for operator and servicing instructions on how to mount and connect
the products using the intended motor connection adapter, please see Installation
du régulateur d'entraînement intégré au moteur [➙ 18] and Plaques adaptatrices
[➙ 69].

Use 75oC copper wires only.

Connection of external motor overtemperature sensing is required.

11.4

Advertising
Ce manuel est liée aux produits suivants: