Gamatronic electronic industries ltd – MaxPower Corp Gamatronic Power+ M100 Manuel d'utilisation

Page 68

Advertising
background image

Gamatronic Electronic Industries Ltd.

60

POWER+ 3x208 V, User Guide, Release 2.1

1 > B

A T E N D

2 > B

A T L O W

3 > -

- - - - -

Alarm set

menu

Option 2

4 > B

A T - H I S E L E C T I

T E M : 1

Figure 8-37: Battery parameters for alarm

F L O A T I N G C

H A R G E S E T U P

V O L T A G E S

E T T I N G : 1 7 0 . 0 V

Alarm set

menu

Option 2

Figure 8-38: Battery floating charge setup for alarm

1 > O

V E R T

E M P E R A T U R E

2 > U

N D E R T

E M P E R A T U R E

Alarm set

menu

Option 7

P L E A S E S

E L E C T

Figure 8-39: Alarm battery temperature menu

S E T O V E R T

E M P E R A T U R E A L A R M V A L U E

( 2 - 9 9 ) D E G R E E S

Alarm

temp.

Option 1

4 5

Figure 8-40: Alarm battery maximum temperature setting

S E T U N D E R T E M P E R A T U R E A L A R M V A L U E
( 1 - 9 8 ) D E G R E E S

Alarm

temp.

Option 2

0 1

Figure 8-41: Alarm battery minimum temperature setting

S E T I N T E G R A T I O N F A C T O R
( 1 - 3 0 )

Alarm set

menu

Option 9

E N T E R =

A

C C E P T 0 5 E S C =

D

I S C A R D

Figure 8-42 :Alarm integration factor setting

The Alarm Integration Factor determines the number of times that the controller polls
and retries to determine the UPS status before deciding on an error status. Setting
the alarm integration factor too low will cause spurious alarms to be generated;
conversely, setting the alarm integration factor too high may result in an alarm only
being raised when it is already too late to take corrective action.

Advertising